13.1.4 SignalsTable 362:SMPPTRC (94) Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionTRINP_3P BOOLEAN 0 Trip all phasesSETLKOUT BOOLEAN 0 Input for setting the circuit breaker lockout functionRSTLKOUT BOOLEAN 0 Input for resetting the circuit breaker lockout functionTable 363:SMPPTRC (94) Output signalsName Type DescriptionTRIP BOOLEAN Common trip signalCLLKOUT BOOLEAN Circuit breaker lockout output (set until reset)13.1.5 SettingsTable 364:SMPPTRC (94) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Enabled Disable/Enable OperationtTripMin 0.000 - 60.000 s 0.001 0.150 Minimum duration of trip output signalTable 365:SMPPTRC (94) Group settings (advanced)Name Values (Range) Unit Step Default DescriptionTripLockout DisabledEnabled- - Disabled On: Activate output (CLLKOUT) and trip latch,Off: Only outputAutoLock DisabledEnabled- - Disabled On: Lockout from input (SETLKOUT) and trip,Off: Only input13.1.6 Operation principleThe duration of a trip output signal from tripping logic common 3-phase outputSMPPTRC (94) is settable (tTripMin). The pulse length should be long enough to securethe breaker opening.For three-pole tripping logic common 3-phase output, SMPPTRC (94) has a single input(TRINP_3P) through which all trip output signals from the protection functions within theIED, or from external protection functions via one or more of the IEDs binary inputs, areSection 13 1MRK 506 335-UUS ALogic530Technical manual