11.14.3 SignalsTable 326:I103GENCMD Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of commandTable 327:I103GENCMD Output signalsName Type DescriptionCMD_OFF BOOLEAN Command output OFFCMD_ON BOOLEAN Command output ON11.14.4 SettingsTable 328:I103GENCMD Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)PulseLength 0.000 - 60.000 s 0.001 0.400 Pulse lengthInfNo 1 - 255 - 1 1 Information number for command output(1-255)11.15 IED commands with position and select for IEC60870-5-103 I103POSCMD11.15.1 FunctionalityI103POSCMD has double-point position indicators that are getting the position value asan integer (for example from the POSITION output of the SCSWI function block) andsending it over IEC 60870-5-103 (1=OPEN; 2=CLOSE). .The standard does not definethe use of values 0 and 3 . However, when connected to a switching device, these valuesare transmitted.The BLOCK input will block only the signals in monitoring direction (the positioninformation), not the commands via IEC 60870-5-103. The SELECT input is used toindicate that the monitored apparatus has been selected (in a select-before-operate type ofcontrol)1MRK 506 335-UUS A Section 11Control493Technical manual