14.15.9 Technical dataTable 501:SPVNZBAT Technical dataFunction Range or value AccuracyLower limit for the battery terminalvoltage(60-140) % of Vbat ± 1.0% of set battery voltageReset ratio, lower limit <105 % -Upper limit for the battery terminalvoltage(60-140) % of Vbat ± 1.0% of set battery voltageReset ratio, upper limit >95 % -Timers (0.000-60.000) s ± 0.5% ± 110 msBattery rated voltage 20-250V -14.16 Insulation gas monitoring function SSIMG (63)14.16.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberInsulation gas monitoring function SSIMG - 6314.16.2 FunctionalityInsulation gas monitoring function SSIMG (63) is used for monitoring the circuit breakercondition. Binary information based on the gas pressure in the circuit breaker is used asinput signals to the function. In addition, the function generates alarms based on receivedinformation.14.16.3 Function blockANSI09000129-1-en.vsdSSIMG (63)BLOCKBLK_ALMPRESSURETEMPPRES_ALMPRES_LOSET_P_LOSET_T_LORESET_LOPRESSUREPRES_ALMPRES_LOTEMPTEMP_ALMTEMP_LOANSI09000129 V1 ENFigure 310: SSIMG (63) function block1MRK 506 335-UUS A Section 14Monitoring675Technical manual