Name Values (Range) Unit Step Default DescriptionIHiHiLim 0.0 - 500.0 %IB 0.1 150.0 High High limit in % of IBaseIHiLim 0.0 - 500.0 %IB 0.1 120.0 High limit in % of IBaseILowLim 0.0 - 500.0 %IB 0.1 80.0 Low limit in % of IBaseILowLowLim 0.0 - 500.0 %IB 0.1 60.0 Low Low limit in % of IBaseILimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for alllimits)FrDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sFrZeroDb 0 - 100000 m% 1 500 Zero point clampingFrHiHiLim 0.000 - 100.000 Hz 0.001 65.000 High High limit (physical value)FrHiLim 0.000 - 100.000 Hz 0.001 63.000 High limit (physical value)FrLowLim 0.000 - 100.000 Hz 0.001 47.000 Low limit (physical value)FrLowLowLim 0.000 - 100.000 Hz 0.001 45.000 Low Low limit (physical value)FrLimHyst 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range (common for alllimits)UAmpComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 5% ofVnUAmpComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 30% ofVnUAmpComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%of VnIAmpComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of InIAmpComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30% ofInIAmpComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%of InIAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of InIAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of InIAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In14.1.2.5 Monitored dataTable 424:CVMMXN Monitored dataName Type Values (Range) Unit DescriptionS REAL - MVA Apparent power magnitude ofdeadband valueP REAL - MW Active power magnitude ofdeadband valueQ REAL - MVAr Reactive power magnitude ofdeadband valueTable continues on next page1MRK 506 335-UUS A Section 14Monitoring581Technical manual