Name Type DescriptionWFMASTER BOOLEAN Signal to Slave issued by Master for sequentialreclosingCOUNT3P1 INTEGER Counting the number of three-phase reclosing shot 1COUNT3P2 INTEGER Counting the number of three-phase reclosing shot 2COUNT3P3 INTEGER Counting the number of three-phase reclosing shot 3COUNT3P4 INTEGER Counting the number of three-phase reclosing shot 4COUNT3P5 INTEGER Counting the number of three-phase reclosing shot 5COUNTAR INTEGER Counting total number of reclosing shots11.2.5 SettingsTable 245:SMBRREC (79) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledExternal ctrlEnabled- - External ctrl Disable/ExternalCtrl/Enablet1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing 3phtReset 0.00 - 6000.00 s 0.01 60.00 Duration of the reset timetSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchronism-check OKtTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse durationtCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that CB must be closed beforenew sequence allowstUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicatingUnsuccessful/SuccessfulPriority NoneLowHigh- - None Priority selection between adjacent terminalsNone/Low/HightWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from MasterTable 246:SMBRREC (79) Group settings (advanced)Name Values (Range) Unit Step Default DescriptionNoOfShots 12345- - 1 Maximum number of reclosing shots 1-5StartByCBOpen DisabledEnabled- - Disabled To be set ON if AR is to be started by CB openpositionCBAuxContType NormClosedNormOpen- - NormOpen Select CB auxilary contact type NC/NO forCBPOS inputTable continues on next pageSection 11 1MRK 506 335-UUS AControl366Technical manual