14.20.4 SettingsTable 518:I103MEASUSR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 25 Function type (1-255)InfNo 1 - 255 - 1 1 Information number for measurands (1-255)MaxMeasur1 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 1MaxMeasur2 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 2MaxMeasur3 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 3MaxMeasur4 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 4MaxMeasur5 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 5MaxMeasur6 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 6MaxMeasur7 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 7MaxMeasur8 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 8MaxMeasur9 0.05 -10000000000.00- 0.05 1000.00 Maximum value for measurement on input 914.21 Function status auto-recloser for IEC 60870-5-103I103AR14.21.1 FunctionalityI103AR is a function block with defined functions for autorecloser indications in monitordirection. This block includes the FunctionType parameter, and the information numberparameter is defined for each output signal.Section 14 1MRK 506 335-UUS AMonitoring698Technical manual