Table 457:L4UFCNT Output signalsName Type DescriptionERROR BOOLEAN Error indication on counter limit and/or initial valuesettingsOVERFLOW BOOLEAN Overflow indication on count of greater than MaxValueLIMIT1 BOOLEAN Counted value is larger than or equal to CounterLimit1LIMIT2 BOOLEAN Counted value is larger than or equal to CounterLimit2LIMIT3 BOOLEAN Counted value is larger than or equal to CounterLimit3LIMIT4 BOOLEAN Counted value is larger than or equal to CounterLimit4VALUE INTEGER Counted value14.3.6 SettingsTable 458:L4UFCNT Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledOn- - Disabled Operation Disable / EnableCountType SetResetDBLL or DLLB- - Set Select counting on positive and/or negativesidesCounterLimit1 1 - 65535 - 1 100 Value of the first limitCounterLimit2 1 - 65535 - 1 200 Value of the second limitCounterLimit3 1 - 65535 - 1 300 Value of the third limitCounterLimit4 1 - 65535 - 1 400 Value of the fourth limitMaxValue 1 - 65535 - 1 500 Maximum count valueOnMaxValue StopRollover SteadyRollover Pulsed- - Stop Select if counter stops or rolls over afterreaching maxValue with steady or pulsedoverflow flagInitialValue 0 - 65535 - 1 0 Initial count value after reset of the function14.3.7 Monitored dataTable 459:L4UFCNT Monitored dataName Type Values (Range) Unit DescriptionVALUE INTEGER - - Counted valueSection 14 1MRK 506 335-UUS AMonitoring612Technical manual