Table 406:B16I Output signalsName Type DescriptionOUT INTEGER Output value13.6.5 SettingsThe function does not have any parameters available in local HMI or Protection andControl IED Manager (PCM600)13.6.6 Monitored dataTable 407:B16I Monitored dataName Type Values (Range) Unit DescriptionOUT INTEGER - - Output value13.6.7 Operation principleThe Boolean 16 to integer conversion function (B16I) will transfer a combination of up to16 binary inputs INx, where 1≤x≤16, to an integer. Each INx represents a value accordingto the table below from 0 to 32768. This follows the general formula: INx = 2x-1 where1≤x≤16. The sum of all the values on the activated INx will be available on the outputOUT as a sum of the integer values of all the inputs INx that are activated. OUT is aninteger. When all INx (where 1≤x≤16) are activated, that is = Boolean 1, it corresponds tothat integer 65535 is available on the output OUT. The B16I function is designed forreceiving up to 16 booleans input locally. If the BLOCK input is activated, it will freezethe output at the last value.Values of each of the different OUTx from function block B16I for 1≤x≤16.The sum of the value on each INx corresponds to the integer presented on the output OUTon the function block B16IName of input Type Default Description Value whenactivatedValue whendeactivatedIN1 BOOLEAN 0 Input 1 1 0IN2 BOOLEAN 0 Input 2 2 0IN3 BOOLEAN 0 Input 3 4 0IN4 BOOLEAN 0 Input 4 8 0IN5 BOOLEAN 0 Input 5 16 0IN6 BOOLEAN 0 Input 6 32 0Table continues on next page1MRK 506 335-UUS A Section 13Logic559Technical manual