11.4.5.4 SignalsTable 262:QCBAY Input signalsName Type Default DescriptionLR_OFF BOOLEAN 0 External Local/Remote switch is in Off positionLR_LOC BOOLEAN 0 External Local/Remote switch is in Local positionLR_REM BOOLEAN 0 External Local/Remote switch is in Remote positionLR_VALID BOOLEAN 0 Data representing the L/R switch position is validBL_UPD BOOLEAN 0 Steady signal to block the position updatesBL_CMD BOOLEAN 0 Steady signal to block the commandTable 263:QCBAY Output signalsName Type DescriptionPSTO INTEGER Value for the operator place allocationUPD_BLKD BOOLEAN Update of position is blockedCMD_BLKD BOOLEAN Function is blocked for commandsLOC BOOLEAN Local operation allowedREM BOOLEAN Remote operation allowed11.4.5.5 SettingsTable 264:QCBAY Non group settings (basic)Name Values (Range) Unit Step Default DescriptionAllPSTOValid PriorityNo priority- - Priority Priority of originators11.4.6 Local remote LOCREM11.4.6.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLocal remote LOCREM - -11.4.6.2 FunctionalityThe signals from the local HMI or from an external local/remote switch are applied via thefunction blocks LOCREM and LOCREMCTRL to the Bay control QCBAY functionSection 11 1MRK 506 335-UUS AControl396Technical manual