14.1.4.4 SettingsTable 432:VMMXU Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Operation Disable / EnableGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base ValuegroupsVLDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sVLMax 0 - 4000000 V 1 170000 Maximum valueVLRepTyp CyclicDead bandInt deadband- - Dead band Reporting typeVLAngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range, IntDb: In %sTable 433:VMMXU Non group settings (advanced)Name Values (Range) Unit Step Default DescriptionVLZeroDB 0 - 100000 m% 1 500 Zero point clampingVLHiHilLim 0 - 4000000 V 1 160000 High High limit (physical value)VLHiLim 0 - 4000000 V 1 150000 High limit (physical value)VLLowLim 0 - 4000000 V 1 125000 Low limit (physical value)VLowLowLim 0 - 4000000 V 1 115000 Low Low limit (physical value)VLMin 0 - 4000000 V 1 0 Minimum valueVLLimHys 0.000 - 100.000 V 0.001 5.000 Hysteresis value in % of range and is commonfor all limits14.1.4.5 Monitored dataTable 434:VMMXU Monitored dataName Type Values (Range) Unit DescriptionV_AB REAL - kV V_AB AmplitudeVAB_ANGL REAL - deg VAB AngleV_BC REAL - kV V_BC AmplitudeVBC_ANGL REAL - deg VBC AngleV_CA REAL - kV V_CA AmplitudeVCA_ANGL REAL - deg VCA AngleSection 14 1MRK 506 335-UUS AMonitoring586Technical manual