Name Type DescriptionCOUNT3P4 INTEGER Counting the number of three-phase reclosing shot 4COUNT3P5 INTEGER Counting the number of three-phase reclosing shot 5COUNTAR INTEGER Counting total number of reclosing shots11.3.5 SettingsTable 250:STBRREC (79) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledExternal ctrlEnabled- - External ctrl Disable/ExternalCtrl/EnableARMode 3 phase1/3ph1 phase1ph+1*3ph- - 3 phase AR mode selection e.g. 3ph, 1/3pht1 1Ph 0.000 - 60.000 s 0.001 1.000 Open time for shot 1, single-phaset1 3Ph 0.000 - 60.000 s 0.001 6.000 Open time for shot 1, delayed reclosing 3phtReset 0.00 - 6000.00 s 0.01 60.00 Duration of the reset timetSync 0.00 - 6000.00 s 0.01 30.00 Maximum wait time for synchronism-check OKtTrip 0.000 - 60.000 s 0.001 0.200 Maximum trip pulse durationtCBClosedMin 0.00 - 6000.00 s 0.01 5.00 Minimum time that CB must be closed beforenew sequence allowstUnsucCl 0.00 - 6000.00 s 0.01 30.00 Wait time for CB before indicatingUnsuccessful/SuccessfulPriority NoneLowHigh- - None Priority selection between adjacent terminalsNone/Low/HightWaitForMaster 0.00 - 6000.00 s 0.01 60.00 Maximum wait time for release from MasterTable 251:STBRREC (79) Group settings (advanced)Name Values (Range) Unit Step Default DescriptionNoOfShots 12345- - 1 Maximum number of reclosing shots 1-5StartByCBOpen DisabledEnabled- - Disabled To be set ON if AR is to be started by CB openpositionCBAuxContType NormClosedNormOpen- - NormOpen Select CB auxilary contact type NC/NO forCBPOS inputCBReadyType COOCO- - CO Select type of circuit breaker ready signalCO/OCOTable continues on next pageSection 11 1MRK 506 335-UUS AControl378Technical manual