Name Values (Range) Unit Step Default Description3I2PU 1 - 100 %IB 1 10 Pickup of negative sequence undercurrentelement in % of IBaseOpDVDI DisabledEnabled- - Disabled Operation of change based function Disable/EnableDVPU 1 - 100 %VB 1 60 Pickup of change in phase voltage in % ofVBaseDIPU 1 - 100 %IB 1 15 Pickup of change in phase current in % ofIBaseVPPU 1 - 100 %VB 1 70 Pickup of phase voltage in % of VBase50P 1 - 100 %IB 1 10 Pickup of phase current in % of IBaseSealIn DisabledEnabled- - Enabled Seal in functionality Disable/EnableVSealInPU 1 - 100 %VB 1 70 Pickup of seal-in phase voltage in % of VBaseIDLDPU 1 - 100 %IB 1 5 Pickup for phase current detection in % ofIBase for dead line detectionVDLDPU 1 - 100 %VB 1 60 Pickup for phase voltage detection in % ofVBase for dead line detectionTable 230:SDDRFUF Non group settings (basic)Name Values (Range) Unit Step Default DescriptionGlobalBaseSel 1 - 6 - 1 1 Selection of one of the Global Base Valuegroups10.2.6 Monitored dataTable 231:SDDRFUF Monitored dataName Type Values (Range) Unit Description3I0 REAL - A Magnitude of zero sequencecurrent3I2 REAL - A Magnitude of negativesequence current3V0 REAL - kV Magnitude of zero sequencevoltage3V2 REAL - kV Magnitude of negativesequence voltage1MRK 506 335-UUS A Section 10Secondary system supervision335Technical manual