11.4.2.4 SignalsTable 253:SCSWI Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionPSTO INTEGER 2 Operator place selectionL_SEL BOOLEAN 0 Select signal from local panelL_OPEN BOOLEAN 0 Open signal from local panelL_CLOSE BOOLEAN 0 Close signal from local panelAU_OPEN BOOLEAN 0 Used for local automation functionAU_CLOSE BOOLEAN 0 Used for local automation functionBL_CMD BOOLEAN 0 Steady signal for block of the commandRES_EXT BOOLEAN 0 Reservation is made externallySY_INPRO BOOLEAN 0 Synchronizing function in progressSYNC_OK BOOLEAN 0 Closing is permitted by the synchronism-checkEN_OPEN BOOLEAN 0 Enables open operationEN_CLOSE BOOLEAN 0 Enables close operationXPOS GROUPSIGNAL- Group signal from XCBR/XSWITable 254:SCSWI Output signalsName Type DescriptionEXE_OP BOOLEAN Execute Open commandEXE_CL BOOLEAN Execute Close commandSELECTED BOOLEAN Select conditions are fulfilledSTART_SY BOOLEAN Starts the synchronizing functionPOSITION INTEGER Position indicationOPENPOS BOOLEAN Open position indicationCLOSEPOS BOOLEAN Closed position indicationCMD_BLK BOOLEAN Commands are blockedL_CAUSE INTEGER Latest value of the error indication during commandPOS_INTR BOOLEAN Stopped in intermediate positionXOUT BOOLEAN Execution information to XCBR/XSWI1MRK 506 335-UUS A Section 11Control391Technical manual