Table 25:ZQMPDIS (21) Output signalsName Type DescriptionTRIP BOOLEAN General tripTR_A BOOLEAN Trip signal for L1TR_B BOOLEAN Trip signal for L2TR_C BOOLEAN Trip signal for L3TRZ1 BOOLEAN Trip signal Zone1TRZ2 BOOLEAN Trip signal Zone2TRZ3 BOOLEAN Trip signal Zone3TRZ4 BOOLEAN Trip signal Zone4TRZ5 BOOLEAN Trip signal Zone5PICKUP BOOLEAN PickupPU_A BOOLEAN Start signal for L1PU_B BOOLEAN Start signal for L2PU_C BOOLEAN Start signal for L3PU_Z1 BOOLEAN Start signal Zone1PU_Z2 BOOLEAN Start signal Zone2Z3_PU BOOLEAN Start signal Zone3Z4_PU BOOLEAN Start signal Zone4Z5_PU BOOLEAN Start signal Zone56.1.5 SettingsTable 26:ZQMPDIS (21) Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation DisabledEnabled- - Disabled Disable/Enable OperationCvtFltr DisabledEnabled- - Enabled Enable CVT FilteringLineAng 0.00 - 90.00 Deg 0.01 80.00 Line impedance angle in degrees, common forall zonesKNMag 0.000 - 3.000 - 0.001 0.000 Common ground compensation factormagnitude for Zone 2, 3, 4 & 5KNAng -180 - 180 Deg 1 -15 Common ground compensation factor anglefor Zone 2, 3, 4 & 5IMinPUPG 10 - 30 %IB 1 15 Minimum operating phase current for phase toground loops, % of IBaseIMinPUPP 10 - 30 %IB 1 15 Minimum operating phase current for phase tophase loops, in % of IBaseTable continues on next page1MRK 506 335-UUS A Section 6Impedance protection93Technical manual