11.4.2.5 SettingsTable 255:SCSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptionCtlModel Dir NormSBO Enh- - SBO Enh Specifies control model typePosDependent Always permittedNot perm at 00/11- - Always permitted Permission to operate depending on thepositiontSelect 0.000 - 60.000 s 0.001 30.000 Maximum time between select and executesignalstSynchrocheck 0.00 - 600.00 s 0.01 10.00 Allowed time for synchronism-check to fulfilclose conditionstSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signalsynchronizing in progresstExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command execution totermination11.4.3 Circuit breaker SXCBR11.4.3.1 SignalsTable 256:SXCBR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of functionLR_SWI BOOLEAN 0 Local/Remote switch indication from switchyardOPEN BOOLEAN 0 Pulsed signal used to immediately open the switchCLOSE BOOLEAN 0 Pulsed signal used to immediately close the switchBL_OPEN BOOLEAN 0 Signal to block the open commandBL_CLOSE BOOLEAN 0 Signal to block the close commandBL_UPD BOOLEAN 0 Steady signal for block of the position updatingPOSOPEN BOOLEAN 0 Signal for open position of apparatus from I/OPOSCLOSE BOOLEAN 0 Signal for close position of apparatus from I/OTR_OPEN BOOLEAN 0 Signal for open position of truck from I/OTR_CLOSE BOOLEAN 0 Signal for close position of truck from I/ORS_CNT BOOLEAN 0 Resets the operation counterXIN BOOLEAN 0 Execution information from CSWISection 11 1MRK 506 335-UUS AControl392Technical manual