9.6 Autotuning without Host Reference9.6.6 Automatically Adjusted Function Settings9-319 Tuning9.6.6 Automatically Adjusted Function SettingsYou can specify whether to automatically adjust the following functions during autotuning. Automatic Notch FiltersNormally, set Pn460 to n.1 (Adjust automatically) (default setting).Vibration will be detected during autotuning without a host reference and a notch filter will beadjusted.Set Pn460 to n.0 (Do not adjust automatically) only if you do not change the setting ofthe notch filter before you execute this function. Anti-Resonance Control AdjustmentThis function reduces low vibration frequencies, for which the notch filters cannot be used.Normally, set Pn160 to n.1 (Adjust automatically) (default setting).Vibration will be detected during autotuning without a host reference and anti-resonance con-trol will be automatically adjusted. Vibration SuppressionYou can use vibration suppression to suppress transitional vibration at a low frequency from 1Hz to 100 Hz, which is generated mainly when the machine vibrates during positioning.Normally, set Pn140 to n.1 (Adjust automatically) (default setting).Vibration will be detected during autotuning without a host reference and vibration suppressioncontrol will be automatically set.Set Pn140 = n.0 (Do not adjust automatically) only if you do not change the settings forvibration suppression before you execute autotuning without a host reference.Note: Autotuning without a host reference uses model following control. Therefore, it can be executed only if themode is set to 2 or 3.Parameter Function When Enabled ClassificationPn460(2460h)n.0Do not adjust the first stage notch filter auto-matically during execution of autotuning with-out a host reference, autotuning with a hostreference, and custom tuning.Immediately Tuningn.1(default setting)Adjust the first stage notch filter automaticallyduring execution of autotuning without a hostreference, autotuning with a host reference,and custom tuning.n.0Do not adjust the second stage notch filterautomatically when the tuning-less function isenabled or during execution of autotuningwithout a host reference, autotuning with ahost reference, and custom tuning.n.1(default setting)Adjust the second stage notch filter automati-cally when the tuning-less function is enabledor during execution of autotuning without ahost reference, autotuning with a host refer-ence, and custom tuning.Parameter Function When Enabled ClassificationPn160(2160h)n.0Do not adjust anti-resonance control automat-ically during execution of autotuning without ahost reference, autotuning with a host refer-ence, and custom tuning. Immediately Tuningn.1(default setting)Adjust anti-resonance control automaticallyduring execution of autotuning without a hostreference, autotuning with a host reference,and custom tuning.