10.1.3 Function blockSESRSYNU3PBB1*U3PBB2*U3PLN1*U3PLN2*BLOCKBLKSYNCHBLKSCBLKENERGB1QOPENB1QCLDB2QOPENB2QCLDLN1QOPENLN1QCLDLN2QOPENLN2QCLDUB1OKUB1FFUB2OKUB2FFULN1OKULN1FFULN2OKULN2FFSTARTSYNTSTSYNCHTSTSCTSTENERGAENMODEMENMODESYNOKAUTOSYOKAUTOENOKMANSYOKMANENOKTSTSYNOKTSTAUTSYTSTMANSYTSTENOKUSELFAILB1SELB2SELLN1SELLN2SELSYNPROGRSYNFAILFRDIFSYNFRDERIVAUOKSCUDIFFSCFRDIFFAPHDIFFAFRDIFFMPHDIFFMINADVCLSUDIFFMEFRDIFFMEPHDIFFMEUBUSULINEMODEAENMODEMENIEC08000219_3_en.vsdIEC08000219 V3 ENFigure 96: SESRSYN function block10.1.4 SignalsTable 165:SESRSYN Input signalsName Type Default DescriptionU3PBB1 GROUPSIGNAL- Group signal for phase to earth voltage input L1,busbar 1U3PBB2 GROUPSIGNAL- Group signal for phase to earth voltage input L1,busbar 2U3PLN1 GROUPSIGNAL- Group signal for phase to earth voltage input L1,line 1U3PLN2 GROUPSIGNAL- Group signal for phase to earth voltage input L1,line 2BLOCK BOOLEAN 0 General blockBLKSYNCH BOOLEAN 0 Block synchronizingBLKSC BOOLEAN 0 Block synchro checkBLKENERG BOOLEAN 0 Block energizing checkB1QOPEN BOOLEAN 0 Open status for CB or disconnector connected tobus1Table continues on next pageSection 10 1MRK 511 287-UEN AControl210Technical manual