Table 475:GOOSEMVRCV Output signalsName Type DescriptionMVOUT REAL Measurand value outputDATAVALID BOOLEAN Data valid for measurand value outputCOMMVALID BOOLEAN Communication valid for measurand value outputTEST BOOLEAN Test output14.7.5 SettingsTable 476:GOOSEMVRCV Non group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off/On14.7.6 Operation principleThe DATAVALID output will be HIGH if the incoming message is with valid data.The COMMVALID output will become LOW when the sending IED is under totalfailure condition and the GOOSE transmission from the sending IED does not happen.The TEST output will go HIGH if the sending IED is in test mode.The input of this GOOSE block must be linked in SMT by means ofa cross to receive the float values.The implementation for IEC61850 quality data handling is restrictedto a simple level. If quality data validity is GOOD then theDATAVALID output will be HIGH. If quality data validity isINVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLDDATA then the DATAVALID output will be LOW.14.8 GOOSE function block to receive a single point valueGOOSESPRCV14.8.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberGOOSE function block to receive asingle point valueGOOSESPRCV - -1MRK 511 287-UEN A Section 14Station communication535Technical manual