Name Values (Range) Unit Step Default DescriptionUAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate voltage at100% of UrIAmpComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at 5%of IrIAmpComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at30% of IrIAmpComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to calibrate current at100% of IrIAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of IrIAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of IrIAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of Ir12.1.2.5 Monitored dataTable 341:CVMMXN Monitored dataName Type Values (Range) Unit DescriptionS REAL - MVA Apparent powermagnitude of deadbandvalueP REAL - MW Active power magnitudeof deadband valueQ REAL - MVAr Reactive powermagnitude of deadbandvaluePF REAL - - Power factor magnitudeof deadband valueU REAL - kV Calculated voltagemagnitude of deadbandvalueI REAL - A Calculated currentmagnitude of deadbandvalueF REAL - Hz System frequencymagnitude of deadbandvalue12.1.3 Phase current measurement CMMXU12.1.3.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberPhase current measurement CMMXUISYMBOL-SS V1 EN-1MRK 511 287-UEN A Section 12Monitoring397Technical manual