3.4 SettingsDependent on ordered IED type.Table 1:AISVBAS Non group settings (basic)Name Values (Range) Unit Step Default DescriptionPhaseAngleRef TRM - Channel 1TRM - Channel 2TRM - Channel 3TRM - Channel 4TRM - Channel 5TRM - Channel 6TRM - Channel 7TRM - Channel 8TRM - Channel 9TRM - Channel 10AIM - Channel 1AIM - Channel 2AIM - Channel 3AIM - Channel 4AIM - Channel 5AIM - Channel 6AIM - Channel 7AIM - Channel 8AIM - Channel 9AIM - Channel 10- - TRM - Channel 1 Reference channel for phase anglepresentationTable 2:TRM_6I_4U Non group settings (basic)Name Values (Range) Unit Step Default DescriptionCTStarPoint1 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTsec1 0.1 - 10.0 A 0.1 1 Rated CT secondary currentCTprim1 1 - 99999 A 1 1000 Rated CT primary currentCTStarPoint2 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTsec2 0.1 - 10.0 A 0.1 1.0 Rated CT secondary currentCTprim2 1 - 99999 A 1 1000 Rated CT primary currentCTStarPoint3 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTsec3 0.1 - 10.0 A 0.1 1 Rated CT secondary currentCTprim3 1 - 99999 A 1 1000 Rated CT primary currentCTStarPoint4 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTsec4 0.1 - 10.0 A 0.1 1.0 Rated CT secondary currentCTprim4 1 - 99999 A 1 1000 Rated CT primary currentCTStarPoint5 FromObjectToObject- - ToObject ToObject= towards protected object,FromObject= the oppositeCTsec5 0.1 - 10.0 A 0.1 1 Rated CT secondary currentCTprim5 1 - 99999 A 1 1000 Rated CT primary currentTable continues on next page1MRK 511 287-UEN A Section 3Analog inputs45Technical manual