however gives as a result that it can take long time, up to several minutes, before a newvalue is stored in the flash memory. And if a new CNTGGIO value is not stored beforeauxiliary power interruption, it will be lost. CNTGGIO stored values in flash memorywill however not be lost at an auxiliary power interruption.The function block also has an input BLOCK. At activation of this input all sixcounters are blocked. The input can for example, be used for blocking the counters attesting.The function block has an input RESET. At activation of this input all sixcounters are set to 0.All inputs are configured via PCM600.12.2.7.1 ReportingThe content of the counters can be read in the local HMI.Reset of counters can be performed in the local HMI and a binary input.Reading of content can also be performed remotely, for example from a IEC 61850client. The value can also be presented as a measuring value on the local HMIgraphical display.12.2.8 Technical dataTable 372:CNTGGIO technical dataFunction Range or value AccuracyCounter value 0-100000 -Max. count up speed 10 pulses/s (50% duty cycle) -12.3 Function descriptionFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberLimit counter L4UFCNT -12.3.1 Limit counter L4UFCNT12.3.2 IntroductionLimit counter (L4UFCNT) provides a settable counter with four independent limitswhere the number of positive and/or negative flanks on the input signal are countedagainst the setting values for limits. The output for each limit is activated when thecounted value reaches that limit.1MRK 511 287-UEN A Section 12Monitoring423Technical manual