Name Type DescriptionCLOSEPOS BOOLEAN Apparatus closed positionTR_POS INTEGER Truck position indicationCNT_VAL INTEGER Operation counter valueL_CAUSE INTEGER Latest value of the error indication during command10.3.4.5 SettingsTable 184:SXSWI Non group settings (basic)Name Values (Range) Unit Step Default DescriptiontStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus tomove after a commandtIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate positionAdaptivePulse Not adaptiveAdaptive- - Not adaptive Output resets when a new correct endposition is reachedtOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open commandtClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close commandSwitchType Load BreakDisconnectorEarthing SwitchHS Earthing Switch- - Disconnector 1=LoadBreak,2=Disconnector,3=EarthSw,4=HighSpeedEarthSwSuppressMidPos OffOn- - On Mid-position is suppressed during thetime tIntermediate10.3.5 Bay control QCBAY10.3.5.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberBay control QCBAY - -10.3.5.2 FunctionalityThe Bay control QCBAY function is used together with Local remote and localremote control functions to handle the selection of the operator place per bay. QCBAYalso provides blocking functions that can be distributed to different apparatuses withinthe bay.Section 10 1MRK 511 287-UEN AControl242Technical manual