12.4.7 Technical dataTable 390:DRPRDRE technical dataFunction Range or value AccuracyCurrent recording - ± 1,0% of Ir at I ≤ Ir± 1,0% of I at I > IrVoltage recording - ± 1,0% of Ur at U ≤ Ur± 1,0% of U at U > UrPre-fault time (0.05–3.00) s -Post-fault time (0.1–10.0) s -Limit time (0.5–8.0) s -Maximum number of recordings 100, first in - first out -Time tagging resolution 1 ms See time synchronizationtechnical dataMaximum number of analog inputs 30 + 10 (external + internallyderived)-Maximum number of binary inputs 96 -Maximum number of phasors in theTrip Value recorder per recording30 -Maximum number of indications in adisturbance report96 -Maximum number of events in theEvent recording per recording150 -Maximum number of events in theEvent list1000, first in - first out -Maximum total recording time (3.4 srecording time and maximum numberof channels, typical value)340 seconds (100 recordings) at50 Hz, 280 seconds (80recordings) at 60 Hz-Sampling rate 1 kHz at 50 Hz1.2 kHz at 60 Hz-Recording bandwidth (5-300) Hz -12.5 Indications12.5.1 FunctionalityTo get fast, condensed and reliable information about disturbances in the primary and/or in the secondary system it is important to know, for example binary signals thathave changed status during a disturbance. This information is used in the shortperspective to get information via the local HMI in a straightforward way.There are three LEDs on the local HMI (green, yellow and red), which will displaystatus information about the IED and the Disturbance recorder function (triggered).The Indication list function shows all selected binary input signals connected to theDisturbance recorder function that have changed status during a disturbance.1MRK 511 287-UEN A Section 12Monitoring455Technical manual