10.7.5 SettingsThe function does not have any parameters available in Local HMI or Protection andControl IED Manager (PCM600).10.7.6 Operation principleUpon receiving the input signals, the IEC 61850 generic communication I/O functions(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipmentor system that requests these signals. To be able to get the signals, PCM600 must beused to define which function block in which equipment or system should receive thisinformation.10.8 Single point generic control 8 signals SPC8GGIO10.8.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberSingle point generic control 8 signals SPC8GGIO - -10.8.2 FunctionalityThe Single point generic control 8 signals SPC8GGIO function block is a collectionof 8 single point commands, designed to bring in commands from REMOTE(SCADA) to those parts of the logic configuration that do not need extensivecommand receiving functionality (for example, SCSWI). In this way, simplecommands can be sent directly to the IED outputs, without confirmation. Thecommands can be pulsed or steady with a settable pulse time.10.8.3 Function blockSPC8GGIOBLOCKPSTO^OUT1^OUT2^OUT3^OUT4^OUT5^OUT6^OUT7^OUT8IEC09000086_1_en.vsdIEC09000086 V1 ENFigure 156: SPC8GGIO function block1MRK 511 287-UEN A Section 10Control329Technical manual