12.19.3 SignalsTable 432:I103MEAS Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of service value reportingIL1 REAL 0.0 Service value for current phase L1IL2 REAL 0.0 Service value for current phase L2IL3 REAL 0.0 Service value for current phase L3IN REAL 0.0 Service value for residual current INUL1 REAL 0.0 Service value for voltage phase L1UL2 REAL 0.0 Service value for voltage phase L2UL3 REAL 0.0 Service value for voltage phase L3UL1L2 REAL 0.0 Service value for voltage phase-phase L1-L2UN REAL 0.0 Service value for residual voltage UNP REAL 0.0 Service value for active powerQ REAL 0.0 Service value for reactive powerF REAL 0.0 Service value for system frequency12.19.4 SettingsTable 433:I103MEAS Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)MaxIL1 1 - 99999 A 1 3000 Maximum current phase L1MaxIL2 1 - 99999 A 1 3000 Maximum current phase L2MaxIL3 1 - 99999 A 1 3000 Maximum current phase L3MaxIN 1 - 99999 A 1 3000 Maximum residual current INMaxUL1 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L1MaxUL2 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L2MaxUL3 0.05 - 2000.00 kV 0.05 230.00 Maximum voltage for phase L3MaxUL1-UL2 0.05 - 2000.00 kV 0.05 400.00 Maximum voltage for phase-phase L1-L2MaxUN 0.05 - 2000.00 kV 0.05 230.00 Maximum residual voltage UNMaxP 0.00 - 2000.00 MW 0.05 1200.00 Maximum value for active powerMaxQ 0.00 - 2000.00 MVA 0.05 1200.00 Maximum value for reactive powerMaxF 45.0 - 66.0 Hz 1.0 51.0 Maximum system frequency1MRK 511 287-UEN A Section 12Monitoring503Technical manual