12.21.3 SignalsTable 436:I103AR Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting16_ARACT BOOLEAN 0 Information number 16, auto-recloser active128_CBON BOOLEAN 0 Information number 128, circuit breaker on by auto-recloser130_BLKD BOOLEAN 0 Information number 130, auto-recloser blocked12.21.4 SettingsTable 437:I103AR Non group settings (basic)Name Values (Range) Unit Step Default DescriptionFunctionType 1 - 255 - 1 1 Function type (1-255)12.22 Function status earth-fault for IEC 60870-5-103I103EF12.22.1 FunctionalityI103EF is a function block with defined functions for earth fault indications in monitordirection. This block includes the FunctionType parameter, and the informationnumber parameter is defined for each output signal.12.22.2 Function blockIEC10000290-1-en.vsdI103EFBLOCK51_EFFW52_EFREVIEC10000290 V1 ENFigure 245: I103EF function block12.22.3 SignalsTable 438:I103EF Input signalsName Type Default DescriptionBLOCK BOOLEAN 0 Block of status reporting51_EFFW BOOLEAN 0 Information number 51, earth-fault forward52_EFREV BOOLEAN 0 Information number 52, earth-fault reverseSection 12 1MRK 511 287-UEN AMonitoring506Technical manual