Name Type DescriptionCLOSEPOS BOOLEAN Apparatus closed positionTR_POS INTEGER Truck position indicationCNT_VAL INTEGER Operation counter valueL_CAUSE INTEGER Latest value of the error indication during command10.3.3.5 SettingsTable 181:SXCBR Non group settings (basic)Name Values (Range) Unit Step Default DescriptiontStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus tomove after a commandtIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate positionAdaptivePulse Not adaptiveAdaptive- - Not adaptive Output resets when a new correct endposition is reachedtOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open commandtClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close commandSuppressMidPos OffOn- - On Mid-position is suppressed during thetime tIntermediate10.3.4 Circuit switch SXSWI10.3.4.1 IdentificationFunction description IEC 61850identificationIEC 60617identificationANSI/IEEE C37.2device numberCircuit switch SXSWI - -10.3.4.2 FunctionalityThe purpose of Circuit switch (SXSWI) function is to provide the actual status ofpositions and to perform the control operations, that is, pass all the commands toprimary apparatuses in the form of disconnectors or earthing switches via binaryoutput boards and to supervise the switching operation and position.Section 10 1MRK 511 287-UEN AControl240Technical manual