Table 407:LMBRFLO Output signalsName Type DescriptionCALCMADE BOOLEAN Fault calculation madeFLT_X REAL Reactive distance to faultBCD_80 BOOLEAN Distance in binary coded data, bit represents 80%BCD_40 BOOLEAN Distance in binary coded data, bit represents 40%BCD_20 BOOLEAN Distance in binary coded data, bit represents 20%BCD_10 BOOLEAN Distance in binary coded data, bit represents 10%BCD_8 BOOLEAN Distance in binary coded data, bit represents 8%BCD_4 BOOLEAN Distance in binary coded data, bit represents 4%BCD_2 BOOLEAN Distance in binary coded data, bit represents 2%BCD_1 BOOLEAN Distance in binary coded data, bit represents 1%12.14.5 SettingsTable 408:LMBRFLO Group settings (basic)Name Values (Range) Unit Step Default DescriptionR1A 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance A (near end)X1A 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance A (near end)R1B 0.001 - 1500.000 ohm/p 0.001 2.000 Source resistance B (far end)X1B 0.001 - 1500.000 ohm/p 0.001 12.000 Source reactance B (far end)R1L 0.001 - 1500.000 ohm/p 0.001 2.000 Positive sequence line resistanceX1L 0.001 - 1500.000 ohm/p 0.001 12.500 Positive sequence line reactanceR0L 0.001 - 1500.000 ohm/p 0.001 8.750 Zero sequence line resistanceX0L 0.001 - 1500.000 ohm/p 0.001 50.000 Zero sequence line reactanceR0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual resistanceX0M 0.000 - 1500.000 ohm/p 0.001 0.000 Zero sequence mutual reactanceLineLengthUnit kilometermiles- - kilometer Line length unitLineLength 0.0 - 10000.0 - 0.1 40.0 Length of lineTable 409:LMBRFLO Non group settings (basic)Name Values (Range) Unit Step Default DescriptionDrepChNoIL1 1 - 30 Ch 1 1 Recorder input number recording phasecurrent, IL1DrepChNoIL2 1 - 30 Ch 1 2 Recorder input number recording phasecurrent, IL2DrepChNoIL3 1 - 30 Ch 1 3 Recorder input number recording phasecurrent, IL3DrepChNoIN 0 - 30 Ch 1 4 Recorder input number recording residualcurrent, INTable continues on next page1MRK 511 287-UEN A Section 12Monitoring473Technical manual