Name Type Default DescriptionSET_L_LO BOOLEAN 0 Set level lockoutSET_T_LO BOOLEAN 0 Set temperature lockoutRESET_LO BOOLEAN 0 Reset level and temperature lockoutTable 424:SSIML Output signalsName Type DescriptionLEVEL REAL Level service valueLVL_ALM BOOLEAN Level below alarm levelLVL_LO BOOLEAN Level below lockout levelTEMP REAL Temperature of the insulation mediumTEMP_ALM BOOLEAN Temperature above alarm levelTEMP_LO BOOLEAN Temperature above lockout level12.17.5 SettingsTable 425:SSIML Group settings (basic)Name Values (Range) Unit Step Default DescriptionOperation OffOn- - Off Operation Off / OnLevelAlmLimit 0.00 - 25.00 - 0.01 5.00 Alarm setting for levelLevelLOLimit 0.00 - 25.00 - 0.01 3.00 Level lockout settingTempAlarmLimit -40.00 - 200.00 - 0.01 30.00 Temperature alarm level setting of themediumTempLOLimit -40.00 - 200.00 - 0.01 30.00 Temperature lockout level of the mediumtLevelAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for level alarmtLevelLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for level lockout indicationtTempAlarm 0.000 - 60.000 s 0.001 0.000 Time delay for temperature alarmtTempLockOut 0.000 - 60.000 s 0.001 0.000 Time delay for temperture lockouttResetLevelAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for level alarmtResetLevelLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for level lockouttResetTempLO 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture lockouttResetTempAlm 0.000 - 60.000 s 0.001 0.000 Reset time delay for temperture alarm12.17.6 Operation principleInsulation liquid monitoring function SSIML is used to monitor oil level in the circuitbreaker. Two binary output signals are used from the circuit breaker to initiate alarmsignals, level below alarm level and level below lockout level. If the input signalLVL_ALM is high, which indicate that the oil level in the circuit breaker is belowalarm level, the output signal LVL_ALM, level below alarm level, will be initiated1MRK 511 287-UEN A Section 12Monitoring487Technical manual