Parameters ASDA-B2-F7-34 September, 201571.5 kW 602 kW 1003 kW 100Following describes the setting value of P1-52 and P1-53 when connecting regenerative resistorwith different method:External regenerative resistorC1 kW, 10 ΩP Setting:P1-52 = 10 (Ω)P1-53 = 1000 (W)P1-54 PER Position Completed Range Address: 016CH016DHOperationalInterface: Panel / Software Communication RelatedSection: Table 7.2Default: 12800 ControlMode: DMCNETUnit: Pulse Range: 0 ~ 1280000Format: DEC Data Size: 32-bitSettings:In DMCNET mode, if the deviation pulse number is smaller than the setting range (the settingvalue of parameter P1-54), DO.TPOS is ON.P1-55 MSPD Maximum Speed Limit Address: 016EH016FHOperationalInterface: Panel / Software Communication RelatedSection: -Default: Same as the rated speed of eachmodel.ControlMode: ALLUnit: r/min Range: 10 ~ max.speedFormat: DEC Data Size: 16-bitSettings:The default of the max. speed of servo motor is set to the rated speed.C1 kW, 10 ΩP1 kW, 10 ΩExternal regenerative resistor(serial connection)Setting:P1-52 = 20 (Ω)P1-53 = 2000 (W)C1 kW, 10 ΩP1 kW, 10 ΩExternal regenerative resistor(parallel connection )Setting:P1-52 = 5 (Ω)P1-53 = 2000 (W)