DVP- ES2/ EX2/ SS2/ SA2/ SX2/ SE&TP O pe r a t i on Ma nua l - Pr ogr am m i ng2- 16SpecialM Function ES2EX2 SS2 SA2SE SX2OFFONSTOPRUNRUNSTOPAttrib. Latch-ed DefaultM1113 Switching clock pulse of Y2 for PWMinstruction (ON: 100us; OFF: 1ms) ○ ○ ○ ○ OFF OFF - R/W NO OFFM1119* Enable 2-speed output function ofDDRVI/DDRVA instructions ○ ╳ ○ ○ OFF OFF OFF R/W NO OFFM1120*Retaining the communication setting ofCOM2 (RS-485), modifying D1120 will beinvalid when M1120 is set.○ ○ ○ ○ OFF OFF - R/W NO OFFM1121 For COM2(RS-485), data transmissionready ○ ○ ○ ○ OFF OFF - R NO OFFM1122 For COM2(RS-485), sending request ○ ○ ○ ○ OFF OFF - R/W NO OFFM1123 For COM2(RS-485), data receivingcompleted ○ ○ ○ ○ OFF OFF - R/W NO OFFM1124 For COM2(RS-485), data receiving ready ○ ○ ○ ○ OFF OFF - R/W NO OFFM1125 For COM2(RS-485), communication readystatus reset ○ ○ ○ ○ OFF OFF OFF R/W NO OFFM1126 For COM2(RS-485), set STX/ETX as userdefined or system defined ○ ○ ○ ○ OFF OFF OFF R/W NO OFFM1127For COM2(RS-485), data sending /receiving / converting completed. (RSinstruction is not supported)○ ○ ○ ○ OFF OFF OFF R/W NO OFFM1128 For COM2(RS-485),Transmitting/Receiving status Indication ○ ○ ○ ○ OFF OFF OFF R/W NO OFFM1129 For COM2(RS-485), receiving time out ○ ○ ○ ○ OFF OFF - R/W NO OFFM1130 For COM2(RS-485), STX/ETX selection ○ ○ ○ ○ OFF OFF - R/W NO OFFM1131For COM2(RS-485), ON whenMODRD/RDST/MODRW data is beingconverted from ASCII to Hex○ ○ ○ ○ OFF OFF - R NO OFFM1132 ON when there are no communicationrelated instructions in the program ○ ○ ○ ○ OFF - - R NO OFFM1136* For COM3(RS-485/USB), retainingcommunication setting ○ ╳ ○ ○ OFF - - R/W NO OFFM1137 Retain DNET mapping data during non-executing period ╳ ╳ ○ ○ - - - R/W NO OFFM1138*For COM1 (RS-232), retainingcommunication setting. Modifying D1036will be invalid when M1138 is set.○ ○ ○ ○ OFF - - R/W NO OFFM1139* For COM1(RS-232), ASCII/RTU modeselection (OFF: ASCII; ON: RTU) ○ ○ ○ ○ OFF - - R/W NO OFFM1140 For COM2 (RS-485), MODRD / MODWR/ MODRW data receiving error ○ ○ ○ ○ OFF OFF - R NO OFFM1141 For COM2 (RS-485), MODRD / MODWR/ MODRW parameter error ○ ○ ○ ○ OFF OFF - R NO OFFM1142 Data receiving error of VFD-A handyinstructions ○ ○ ○ ○ OFF OFF - R NO OFFM1143* For COM2(RS-485), ASCII/RTU modeselection (OFF: ASCII; ON: RTU) ○ ○ ○ ○ OFF - - R/W NO OFFM1148After the instruction DELAY is executed,the execution of the program followingDELAY is delayed for 5us.V3.2 V3.0 V2.6V1.4 V2.4 OFF OFF - R/W NO OFFM1156*Enabling the mask and alignment markfunction on I400/I401(X4) correspondingto Y0○ ○ ○ ○ OFF OFF - R/W NO OFFM1158*Enabling the mask and alignment markfunction on I600/I601(X6) correspondingto Y2○ ○ ○ ○ OFF OFF - R/W NO OFFM1161 8/16 bit mode (ON = 8 bit mode) ○ ○ ○ ○ OFF - - R/W NO OFFM1162Switching between decimal integer andbinary floating point for SCLP instruction.ON: binary floating point; OFF: decimalinteger○ ○ ○ ○ OFF - - R/W NO OFFM1167 16-bit mode for HKY input ○ ○ ○ ○ OFF - - R/W NO OFFM1168 Designating work mode of SMOV ○ ○ ○ ○ OFF - - R/W NO OFFM1177Enable the communication instruction forDelta VFD series inverter.ON: VFD-A (Default), OFF: other modelsof VFD○ ○ ○ ○ OFF - - R/W NO OFF