DVP- ES2/ EX2/ SS2/ SA2/ SX2/ SE&TP O pe r a t i on Ma nua l - Pr ogr am m i ng4- 10An example of exception response of command code 01H and exception 02H:Sent message:Field Name Example (Hex)START No data input ≥ 10 msSlave Address 01Command code 01Starting Address 0400Number of Points 0010CRC CHK Low 3CCRC CHK High F6END No data input ≥ 10 msFeedback message:Field Name Example (Hex)START No data input ≥ 10 msSlave Address 01Function 81Exception Code 02CRC CHK Low C1CRC CHK High 91END No data input ≥ 10 ms4.4 PLC Device AddressDevice RangeEffective Range MODBUSAddress AddressES2/EX2 SS2 SA2/SESX2S 000~255000~1023 000~1023000001~000256 0000~00FFS 256~511 000257~000512 0100~01FFS 512~767 000513~000768 0200~02FFS 768~1023 000769~001024 0300~03FFX 000~377 (Octal) 000~377 000~377 101025~101280 0400~04FFY 000~377 (Octal) 000~377 000~377 001281~001536 0500~05FFT 000~255 bit 000~255 000~255 001537~001792 0600~06FF000~255 word 000~255 000~255 401537~401792 0600~06FFM 000~2550000~40950000~4095 002049~0035840800~08FFM 256~511 0900~09FFM 512~767 0A00~0AFFM 768~1023 0B00~0BFFM 1024~1279 0C00~0CFFM 1280~1535 0D00~0DFF