B.2 b: ApplicationApplication parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PIDcontrol, the Dwell function, Energy Savings, and a variety of other application-related settings.u b1: Operation Mode SelectionNo.(Addr.Hex) Name LCD Display Description Values Pageb1-01(0180) Frequency ReferenceSelection 1Ref Source 10: Operator1: Analog Input2: Serial Com3: Option PCB4: Pulse Input0: Digital operator1: Analog input terminals2: MEMOBUS/Modbus communications3: Option PCB4: Pulse input (terminal RP)Default: 1Range: 0 to 4 136b1-02(0181) Run CommandSelection 1Run Source 10: Operator1: Digital Inputs2: Communication3: Option PCB0: Digital operator1: Digital input terminals2: MEMOBUS/Modbus communications3: Option PCBDefault: 1Range: 0 to 3 138b1-03(0182) Stopping MethodSelectionStopping Method0: Ramp to Stop1: Coast to Stop2: DCInj to Stop3: Coast w/Timer0: Ramp to stop1: Coast to stop2: DC Injection Braking to stop3: Coast with timerDefault: 0Range: 0 to 3<1>138b1-04(0183) Reverse OperationSelectionReverse Oper0: Reverse Enabled1: Reverse Disabled0: Reverse enabled.1: Reverse disabled. Default: 0Range: 0, 1 –b1-05(0184)Action Selection belowMinimum OutputFrequencyZero-Speed Oper0: RUN at Freq Ref1: STOP2: RUN at Min FreqRUN at Zero PRM0: Operates according to frequency reference (E1-09 isdisabled).1: Output shuts off (coast to stop if less than E1-09).2: Operates according to E1-09 (frequency reference set toE1-09).3: Zero speed (frequency reference becomes zero when less thanE1-09).Default: 0Range: 0 to 3 –b1-06(0185) Digital Input Reading Cntl Input Scans0: 1 Scan1: 2 Scans0: Input status is read once and processed immediately (forquicker response)1: Input is read twice and processed only if the status is the samein both readings (robust against noisy signals)Default: 1Range: 0, 1 –b1-07(0186) LOCAL/REMOTE RunSelectionLOC/REM Dur Run0: Cycle Extrn RUN1: Accept Extrn RUN0: An external Run command must be cycled at the new sourcein order to be activated.1: An external Run command at the new source is acceptedimmediately.Default: 0Range: 0, 1 –b1-08(0187) Run Command Selectionin Programming ModeRUN dur PRG Mode0: RunDisabled@PRG1: Run Enabled@PRG2: Prg only @ Stop0: Run command is not accepted while in Programming Mode.1: Run command is accepted while in Programming Mode.2: Prohibit entering Programming Mode during run. Default: 0Range: 0 to 2 –b1-14(01C3) Phase Order Selection Rotation Sel0: Standard1: SwitchPhaseOrder0: Standard1: Switch phase order (reverses the direction of the motor) Default: 0Range: 0, 1 –b1-15(01C4) Frequency ReferenceSelection 2Ref Source 20: Operator1: Analog Input2: Serial Com3: Option PCB4: Pulse InputEnabled when an input terminal set for “External reference”(H1-oo = 2) closes.0: Digital operator1: Terminals (analog input terminals)2: MEMOBUS/Modbus communications3: Option card4: Pulse train inputDefault: 0Range: 0 to 4 –b1-16(01C5) Run CommandSelection 2Run Source 20: Operator1: Digital Inputs2: Communication3: Option PCBEnabled when a terminal set for “External reference”(H1-oo = 2) closes.0: Digital operator1: Digital input terminals2: MEMOBUS/Modbus communications3: Option cardDefault: 0Range: 0 to 3 –B.2 b: Application252 YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide