<4> Class L fuse is also approved for this rating.Wiring Fuses for Models 4A0930 and 4A1200NOTICE: If a fuse is blown or an Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of peripheral devicesto identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.Install a fuse on the input side to protect drive wiring and prevent other secondary damage. Wire the fuse so that leakagecurrent in the upper controller power supply will trigger the fuse and shut off the power supply.Select the appropriate fuse from Table 3.2.Table C.9 Input Fuses for Models 4A0930 and 4A1200VoltageClass ModelSelection Input Fuse (Example)Input Voltage Current Pre-arcI2t (A2s) Model Manufacturer Rating Pre-arcI2t (A2s)Three-Phase400 VClass4A0930480 V 1500 A 140000 to3100000CS5F-1200 Fuji Electric AC500 V, 1200 A 2760004A0930 with12-pulserectificationFWH-1200A Bussman AC500 V, 1200 A –FWH-1000A Bussman AC500 V, 1000 A –4A1200480 V 1500 A 320000 to3100000CS5F-1500 Fuji Electric AC500 V, 1500 A 3510004A1200 with12-pulserectificationFWH-1600A Bussman AC500 V, 1600 A –FWH-1200A Bussman AC500 V, 1200 A –n Low Voltage Wiring for Control Circuit TerminalsWire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The externalpower supply shall be a UL Listed Class 2 power supply source or equivalent only.Table C.10 Control Circuit Terminal Power SupplyInput / Output Terminal Signal Power Supply SpecificationsOpen Collector Outputs P1, P2, PC, DM+, DM- Requires class 2 power supplyDigital inputs S1 to S8, SC, HC, H1, H2 Use the internal LVLC power supply of the drive. Use class2 for external power supply.Analog inputs / outputs +V, -V, A1, A2, A3, AC, AM, FM Use the internal LVLC power supply of the drive. Use class2 for external power supply.n Drive Short Circuit RatingThe drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vacmaximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by BussmannType FWH or FWP fuses as specified in Factory Recommended Branch Circuit Protection on page 330.u CSA Standards ComplianceFigure C.8 CSA Markn CSA for Industrial Control EquipmentThe drive is CSA-certified as Industrial Control Equipment Class 3211.Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.u Drive Motor Overload ProtectionSet parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motoroverload protection is UL Listed and in accordance with the NEC and CEC.C.2 UL and CSA Standards348 YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide