u L5: Fault RestartNo.(Addr.Hex) Name LCD Display Description Values PageL5-01(049E) Number of Auto RestartAttempts Num of Restarts Sets the number of times the drive may attempt to restart afterthe following faults occur: GF, LF, oC, oH1, ov, PF, rH, rr,oL1, oL2, oL3, oL4, STo, Uv1.Default: 0Min.: 0Max.: 10 –L5-02(049F)Auto Restart FaultOutput OperationSelectionRestart Sel0: Flt Outp Disabld1: Flt Outp Enabled0: Fault output not active.1: Fault output active during restart attempt. Default: 0Range: 0, 1 –L5-04(046C) Fault Reset IntervalTime Flt Reset Wait T Sets the amount of time to wait between performing faultrestarts. Default: 10.0 sMin.: 0.5Max.: 600.0 –L5-05(0467) Fault Reset OperationSelectionFault Reset Sel0: Continuous1: Use L5-04 Time0: Continuously attempt to restart while incrementing restartcounter only at a successful restart (same as F7 and G7).1: Attempt to restart with the interval time set in L5-04 andincrement the restart counter with each attempt (same as V7).Default: 0Range: 0, 1 –u L6: Torque DetectionNo.(Addr.Hex) Name LCD Display Description Values PageL6-01(04A1)Torque DetectionSelection 1Torq Det 1 Sel0: Disabled1: OL Alm at SpdAgr2: OL Alm dur RUN3: OL Flt at SpdAgr4: OL Flt dur RUN5: UL Alm at SpdAgr6: UL Alm dur RUN7: UL Flt at SpdAgr8: UL Flt dur RUN0: Disabled1: oL3 detection only active during speed agree, operationcontinues after detection2: oL3 detection always active during run, operation continuesafter detection3: oL3 detection only active during speed agree, output shutsdown on an oL3 fault4: oL3 detection always active during run, output shuts downon an oL3 fault5: UL3 detection only active during speed agree, operationcontinues after detection6: UL3 detection always active during run, operation continuesafter detection7: UL3 detection only active during speed agree, output shutsdown on a UL3 fault8: UL3 detection always active during run, output shuts downon a UL3 faultDefault: 0Range: 0 to 8 –L6-02(04A2) Torque DetectionLevel 1 Torq Det 1 Lvl Sets the overtorque and undertorque detection level. Default: 150%Min.: 0Max.: 300 –L6-03(04A3) Torque DetectionTime 1 Torq Det 1 Time Sets the time an overtorque or undertorque condition must existto trigger torque detection 1. Default: 0.1 sMin.: 0.0Max.: 10.0 –L6-04(04A4)Torque DetectionSelection 2Torq Det 2 Sel0: Disabled1: OL Alm at SpdAgr2: OL Alm dur RUN3: OL Flt at SpdAgr4: OL Flt dur RUN5: UL Alm at SpdAgr6: UL Alm dur RUN7: UL Flt at SpdAgr8: UL Flt dur RUN0: Disabled1: oL4 detection only active during speed agree, operationcontinues after detection2: oL4 detection always active during run, operation continuesafter detection3: oL4 detection only active during speed agree, output shutsdown on an oL4 fault4: oL4 detection always active during run, output shuts downon an oL4 fault5: UL4 detection only active during speed agree, operationcontinues after detection6: UL4 detection always active during run, operation continuesafter detection7: UL4 detection only active during speed agree, output shutsdown on a UL4 fault8: UL4 detection always active during run, output shuts downon a UL4 faultDefault: 0Range: 0 to 8 –L6-05(04A5) Torque DetectionLevel 2 Torq Det 2 Lvl Sets the overtorque and undertorque detection level. Default: 150%Min.: 0Max.: 300 –B.8 L: Protection Function304 YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide