Illustration 5.4 Local Area Connection 2 PropertiesDisable the IPv4 Checksum offload on the networkinterfaces as described in chapter 5.3.1 Network Settings forIndirect Communication.How to set the correct Ethernet POWERLINK® master IPaddress:1. Open the Network and Sharing Center.2. On the left, click on Change adapter settings.3. Right-click on the network interface used forfieldbus communication and select Properties.4. Click on Internet Protocol Version 4 (TCP/IPv4) (thecheckbox must be checked) and then click onProperties.5. Select Use the following IP address and use192.168.100.240 as the IP address and255.255.255.0 as the subnet mask. Leave all otherfields empty.Illustration 5.5 Internet Protocol Version 4 (TCP/IPv4)Properties5.3.3 Network Settings for DirectCommunication with EtherCAT®No EtherCAT®-specific network interface configurationneeds to be performed on the ISD Toolbox host PC.5.4 ISD Toolbox CommissioningSTEP 1: Open the main windowThe Main Window is the basis for all ISD Toolbox function-alities. See chapter 5.5.1 Main Window for more information.STEP 2: Connect to networkNOTICEPre-configure the appropriate communication settings toconnect to a network. See chapter 5.3 ISD ToolboxCommunication for further information.1. In the Main Window toolbar, click on the Connectto bus icon to open the Connect to Networkwindow.2. Select the fieldbus type and the networkinterface to connect to.3. Click on OK to connect.4. Verify that the connection is successful bychecking the status strip in the Main Window.Operation with ISD Toolbox VLT® Integrated Servo Drive ISD® 510 System112 Danfoss A/S © 01/2017 All rights reserved. MG36D10255