8.3 Object 0x2000: SAB TemperaturesThis object shows the temperature measured on the powercard, control card, and SAB card in °C.Attribute ValueIndex 0x2000Description TemperatureObject code ArraySub-index 0x00Description Number of entriesAccess Read onlyPDO mapping NoValue range 0x03Default value 0x03Data type UNSIGNED16Sub-index 0x01LCP parameter number 16-34Description Temperature power cardAccess Read onlyPDO mapping YesObject code VarData type SIGNED16Unit °CSub-index 0x02LCP parameter number 16-39Description Temperature control cardAccess Read onlyPDO mapping YesObject code VarData type SIGNED16Unit °CSub-index 0x03LCP parameter number 16-31Description Temperature SAB cardAccess Read onlyPDO mapping YesObject code VarData type SIGNED16Unit °CTable 8.8 Object 0x2000: SAB Temperatures8.4 Object 0x2001: DC-link Related ValuesThis object shows several DC-link voltages and currents.Attribute ValueIndex 0x2001Description DC-link related valuesObject code RecordAttribute ValueSub-index 0x00Description Number of entriesAccess Read onlyPDO mapping NoValue range 0x07Default value 0x07Sub-index 0x01LCP parameter number 51-73Description DC-link total currentAccess Read onlyPDO mapping YesObject code VarData type REALUnit AmpereSub-index 0x02LCP parameter number –Description UDC 1 currentAccess Read onlyPDO mapping YesObject code VarData type REALUnit AmpereSub-index 0x03LCP parameter number –Description UDC 2 currentAccess Read onlyPDO mapping YesObject code VarData type REALUnit AmpereSub-index 0x04LCP parameter number 16-30Description DC-link voltageAccess Read onlyPDO mapping YesObject code VarData type SIGNED16Unit VoltSub-index 0x05LCP parameter number 51-74Description DC leakage currentAccess Read onlyPDO mapping YesObject code VarData type REALUnit AmpereSub-index 0x06LCP parameter number –Description DC-link voltage readoutSAB Parameter Description Programming GuideMG36D102 Danfoss A/S © 01/2017 All rights reserved. 3598 8