AD 33-855-4 Page 499.3 lnformation Available in the Event ofa Tripln the event of a Trip, the Digitrip RMS Trip Unitprovides information as summarized in Table 9-2for operator use.Table 9-2Data available local to, or remote from, theDigitrip RMS Trip Unit during operation.RMS510RMS610RMS810 & 910Red LEDS light to provide Trip lndication of:Long Delay Trip;Short Delay Trjp;lnstantaneous Trip;Ground Fault Trip;Discriminator/Override Trip (LS and LSG only).XXXXXXXXXXXXXXXAlphanumeric Digital Display Shows:LDT (Coded message for Long Delay Trip);SDT (Coded message for Short Delay Trip);INST (Coded message for lnstantaneous Trip);GNDT (Coded message for Ground Fault Trip);DISC (Coded message for Discriminator Trip);EXTT (Coded message for External Trip via PowerNet);Phase Currents at trip (reading in amps x 1000);Ground Cunent at trip (reading in amps x 1000);Peak Demand (Mega Watts) at trip;Present Demand (Mega Watts);Energy (Mega Watts Hours) at trip;Depress STEP push-button to delete coded message ;and view stored data as selected.XXXXXXXXATR contacts close for remote indication of:Long Delay Trip;Short Delay Trip;Long Delay Trip.XXXXXXCommunications data available lor remote use as master PC:Device Address (set at Trip Unit);Breaker Status Clrip).XXReason for Status:LDT (Coded message for Long Delay Trip);SDT (Coded message for Short Delay Trip);INST (Coded message for lnstantaneous Trip);GNDT (Coded message for Ground Fault Trip);DISC (Coded message for Discriminator Trip);EXTT (Coded message for External Trip via PowerNet);Phase Currents at trip (reading in amps x 1000);Ground Current at trip (reading in amps x 1000);Peak Demand (Mega Watts) at trip;Present Demand (Mega Watts Hours);Energy (Mega Watts Hours) at trip.ElT.tEtfective 9/01