AD 33-855-4RMS 810 & 910 CELL HARNESSSTYLE NO. 6502C71G036503C57G03CUSTOMERCONNECTIONSCUSTOMERCONNECTIONSAC120ATRCOMCUSTOMEBCONNECTIONSDGLD\lFSCHLACCOMCELL INTERFACE PLUG(RECEIVES EXTERNAL HARNESS)Terminal BlockPoint & Marking DescriPtionTBl-1 DG Zone lnterlock Digital GroundTBl-2 Gour Zone lnterlock Ground OutputTBl-3 GtN Zone lnterlock Ground lnputTB1-4 5691 Zone lnterlock Short Delay OutputTB1-5 StN Zone lnterlock Short Delay lnputTB1-6 ACCOI\i] ATR 120 Vac lnput CommfB2-1 AC 12O ATR 120 Vac lnput PowerTB2-2 ATRCOI\4 ATR Alarm Contact Common-TB2-3 LD ATF Long Delay TriP Alarm.f B2-4 GF ATR Ground Fault Trip Alarm.TB2-5 SC ATR Short Circuit Alarm.T82-6 HL ATR High Load Alarm.Terminal BlockPoint & Marking DescriPtionTB3- 1 CC1 PowerNet Contact Output to BreakerRemote Close Contact*rB3-2 CC2 PowerNet Contact Output to BreakerRemote Close Contact*TB3-3 COMI\,ll PowerNet Twisted Pair ConnectionTB3-4 COMI\,2 PowerNet Twisted Pair ConnectionTB3-5 Free Terminal for Twisted Pair Shield, etc.T83-6 Free Terminal for Twisted Pair Shield, etc.cc1cc2COMMlcot\4M2NOTICE:.1. Zone lnterlock Jumpers slX-s6y1 and Glx-G6g1 must be installed on TB1 or Breaker will trip instantaneouslyon Short Time and Ground Fault Delay functions. Remove jumpers ONLY if Zone Interlocking is required.2. All wiring terminators shown are furnished complete with Fetrofit Kit Wiring Harness, except those indicated ascustomer connections..ATR contacts are rated at 1 ampere at 120 VAC o|I ampere at 28 VDC.HL COMM1Fig. 12-14 Digitrip RMS 810 & 910 Cell HarnessE:T.il Effective 9 /01