AD 33-855-4 Page 5710.3 ldentification of Trip Unit, Breaker, andSwitchgear CellYour Digitrip RMS Retrofit Kit includes identifica-tion labels for the Digitrip RMS Trip Unit, theBreaker Element Faceplate, and the inside of theSwitchgear Cell Door. lt is important to identify allthree, especially when the Trip Unit has aPowerNet address (Models 810 & 910 only).10.4 The Power Relay Module (ATR)RMS 610, 810, & 910 Retrofit Kits include thePower Relay Module (ATR), which is mountedintegral to the RMS Trip Unit. The ATR input andoutput signals are extracted from the Trip Unit PlugJ4 through the External Harness as shown inFigure 12-9. The Breaker External Harness plugsto the Cell Harness Assembly, which includesprovisions for external wiring connections asshown in Figure 6-1 . Figure 10-8 shows typicalATR 120 VAC source input and dry contact alarmoutput connections for remote alarm indication.10.5 Communications and PowerNetRMS 810 & 910 Retrofit Kits include communica-tions capability when Used with Cutler-Hammer'sPowerNet System. Each RMS Trip Unit includes anlntegrated Communications Chip that permits theextraction of Trip Unit data and the implementationof Breaker close and trip commands from a remotemaster computer. Communication is accomplishedfrom the Trip Unit to the master computer via radiofrequency signal over a twisted pair communica-tions network. The communications signal(COMM1 and COMM2) are extracted from Trip UnitPlug J3 through the External Harness as shown inFigure 12-10. The Breaker External Harness plugsto the Cell Harness Assembly, which includesprovisions for external wiring connections asshown in Figure 7-1 . Figures 1 0-9 through 1 0-12show typical Cell wiring provisions if the PowerNetcomputer close feature is to be utilized.TYPICAL IBM ORIBM COI\-,IPATIBLECOI\4PUTEBASSFMBLIESELECTBONICMOTOB (AEl\rl)olEloldlnCUT-OFF SHIELD ATDEVICE - DO NOT GBOUNDBAUD BATEAND3 DIGITNCO[4ADDBESSVIEW AO Feferio circuit breaker connecl o. dagrams referenced in Secton 6 for acilai connectionsO i,lodular te eph one co.neclor,Type RJ11, supplied by useLO Ground shieldi.q al computer and AEM (cable lo P1 only)as shown.where devices arc daisv-chainednlerconneci shield ng, bul do.ol ground lhe connecllon.O 1/2 watl ca6on resislor required al iasl breake. SeeT.D.17_5r3.Fig. 10-7 Terminating Resistor LocationFifective g/01 ElT.il