Powering down/up applications (examples)Servicing the Network Management Module – 1834. Set the OS shutdown duration to the time needed for your server to shutdown gracefully.This will make sure IPP shutdowns your servers before the load segment is powered down.As a result, it will define the overall shutdown sequence duration for each load segments.4.3.1.4 Step 3: Power outage policy settings4.3.1.4.1 ObjectiveUse load segment policies to define shutdown sequencing.4.3.1.4.2 Resulting setup1. Navigate to Contextual help>>>Protection>>>Shutdown on power outage page of the Network Module2. Make sure Primary is set to: Maximize availability.Storage is the last one to power down, its availability is maximized, and its shutdown will end 30s before the end of backuptime.3. Set Group 1 and Group 2 to: Custom.Applications must shutdown first so Group 1 has been set to start shutdown when on battery for 30s.Servers must shutdown second, so Group 2 has been set to start shutdown when on battery for 210s, so 3min after theapplications.••••For examples of Power outage policy, see the following sections:Maximize availability policy exampleImmediate graceful shutdown policy exampleLoad shedding policy examplesCustom policy examples