ProtectionContextual help of the web interface – 57••••••All agents that are connected to the Network Module are displayed in tables by power sources.PrimaryGroup 1Group 2The 'local agent' setting is used for setting for example a minimum shutdown duration, or a power down delay for a load segmentthat has no registered shutdown agents.One use case would be a load segment that powers network equipment that needs to stay on while servers and storage performtheir orderly shutdown.The tables include the following details:NameDelay (in seconds)OS shutdown duration (in seconds)3.5.2.2 Actions3.5.2.2.1 Set DelaySelect and directly change the setting in the table and then Save.3.5.2.2.2 Set OS shutdown durationSelect and directly change the setting in the table and then Save.3.5.2.3 ExamplesExamples below show the impact of agent settings on the shutdown sequence for a shutdown or an immediate shutdown.••A shutdown time summary is calculated and displayed on the top of the table:Shutdown time: maximum time (Delay + OS shutdown duration + 10s) calculated among all the agents.Immediate shutdown time (OS shutdown duration + 10s) calculated among all the agents.