SNMP trapsInformation – 266Alarm oid at :.1.3.6.1.2.1.33.1.6.3.xDescription when trap 3 Description when trap 4.1.3.6.1.2.1.33.1.6.3.8 Power overload No power overload.1.3.6.1.2.1.33.1.6.3.9 Bypass mode No more on bypass.1.3.6.1.2.1.33.1.6.3.10 Bypass not available Bypass available.1.3.6.1.2.1.33.1.6.3.13 Battery charger fault Battery charger OK.1.3.6.1.2.1.33.1.6.3.14 Not powered Powered (Protected or Not protected).1.3.6.1.2.1.33.1.6.3.16 Fan fault Fan OK.1.3.6.1.2.1.33.1.6.3.17 Battery fuse faultRectifier fuse faultInverter fuse faultBattery fuse OKRectifier fuse OKInverter fuse OK.1.3.6.1.2.1.33.1.6.3.18 Internal failure End of internal failure.1.3.6.1.2.1.33.1.6.3.20 Communication lost Communication recovered.1.3.6.1.2.1.33.1.6.3.23 Shutdown imminent Shutdown canceled7.6.1.2 Xups Mib trapsThis information is for reference only.Trap oid :.1.3.6.1.4.1.534.1.11.4.1.0.xTrap message atoid :.1.3.6.1.4.1.534.1.11.3.0Code HID (For UPS 5P, 5PX, 9SX,9PX, 9xPM, 9xE, 9xPS)Code XCP (For UPS Blade,9395, 9395P, 9395C, 9x55).1.3.6.1.4.1.534.1.11.4.1.0.3Battery discharging 603 2168.1.3.6.1.4.1.534.1.11.4.1.0.4Battery low 604 2056, 2369, 2387.1.3.6.1.4.1.534.1.11.4.1.0.5No more on battery 104, 106 2067.1.3.6.1.4.1.534.1.11.4.1.0.6Battery OK 604 2056, 2369, 2387.1.3.6.1.4.1.534.1.11.4.1.0.7Power overload 208, 306, 705, 80E, 810, 81f, 820,821, 8082102, 2103, 2104, 2325, 2027,2025, 2159, 2160, 2162, 2163,2164, 2165, 2166, 2167, 2323,2342, 2380, 2381, 2382.1.3.6.1.4.1.534.1.11.4.1.0.8Internal failure 002, 010, 105, 300, 301, 302,303, 305, 400, 621, 80d, 814,8162000, 2001, 2047, 2051, 2063,2070, 2077, 2089, 2135, 2147,2224, 2229, 2365, 2384, 2364,2002, 2026, 2028, 2029, 2112,2031, 2048, 2068.1.3.6.1.4.1.534.1.11.4.1.0.9Battery totallydischarged2126.1.3.6.1.4.1.534.1.11.4.1.0.10Inverter internalfailure704 2031