Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 231Input Instance 50: Basic OverloadLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Reserved Reserved Fault/TripInput Instance 51: Extended OverloadLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Reserved Warning Fault/tripInput Instance 52: Basic Motor StarterLength = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Reserved Reserved Reserved Running 1 Reserved Faulted/TrippedInput Instance 54: Extended Motor Starter 2Length = 1 ByteByte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 Reserved Reserved Cntr lfrom Net Ready Running 2 Running 1 Warning Faulted/TripInput Instance 100 (0x64): Status, CurrentLength = 8 BytesByteOffsetSize(bytes) Name Description0 2 Device Status C445_DEVICE_STATUS:Device Bit ArrayBit 0: Faulted/TrippedBit 1: WarningBit 2: Output #1Bit 3: Output #2Bit 4: Input #1Bit 5: Input #2Bit 6: Input #3Bit 7: Input #4Bit 8: Running1Bit 9: Running2Bit 10: Remote or CtrlFromNetBit 11: Output #3Bit 12: ReservedBit 13: InhibitedBit 14: ReadyBit 15: AtRef or Up-To-Speed