Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 25136 4 Warning Reason STATUS_WARNING_BITS, continued0x0000 4000 - high power0x0000 8000 - low power0x0001 0000 - Reserved0x0002 0000 - exceeds starts limit0x0004 0000 - overload0x0008 0000 - stall0x0010 0000 - phase rotation mismatch0x0020 0000 - PTC0x0040 0000 - under voltage restart0x0080 0000 - peak demand0x0100 0000 - HRGF pulse detection40 1 Thermal PilePercentageOVLD_THERMAL_MEM_PERCENT:Thermal Capacity0% Cold Motor100% Will Cause an Overload Trip (%)Input Instance 117 (0x75): Full Monitoring with Basic Analog and Digital InputsLength = 46 BytesByteOffsetSize(bytes) Name Description0 2 Device Status C445_DEVICE_STATUS:Device Bit ArrayBit 0: Faulted/TrippedBit 1: WarningBit 2: Output #1Bit 3: Output #2Bit 4: Input #1Bit 5: Input #2Bit 6: Input #3Bit 7: Input #4Bit 8: Running1Bit 9: Running2Bit 10: Remote or CtrlFromNetBit 11: Output #3Bit 12: ReservedBit 13: InhibitedBit 14: ReadyBit 15: AtRef or Up-To-Speed2 2 Current L1 MOTOR_I_A_SCALED:Phase A (L1) Motor Current Scaled.Scaled by parameter “I Scale Factor.”4 2 Current L2 MOTOR_I_B_SCALED:Phase B (L2) Motor Current Scaled.Scaled by parameter “I Scale Factor.”6 2 Current L3 MOTOR_I_C_SCALED:Phase C (L3) Motor Current Scaled.Scaled by parameter “I Scale Factor.”8 2 Field Inputs LOGIC_INPUT_STATE_BITFIELD:Digital Input Status.Input Instance 116 (0x74): Full Monitoring, continuedLength = 41 BytesByteOffsetSize(bytes) Name Description