Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 2458 4 Trip Reason STATUS_TRIPPED_BITS0x0000 0001 - under voltage0x0000 0002 - over voltage0x0000 0004 - Reserved0x0000 0008 - ground current fault0x0000 0010 - current phase loss0x0000 0020 - current unbalance0x0000 0040 - instantaneous over current0x0000 0080 - jam0x0000 0100 - PF deviation0x0000 0200 - voltage phase loss0x0000 0400 - voltage unbalance0x0000 0800 - freq deviation fast0x0000 1000 - freq deviation slow0x0000 2000 - under current0x0000 4000 - high power0x0000 8000 - low power0x0001 0000 - Reserved0x0002 0000 - exceeds starts limit0x0004 0000 - overload0x0008 0000 - stall0x0010 0000 - phase rotation mismatch0x0020 0000 - PTC0x0040 0000 - under voltage restart0x0080 0000 - peak demand0x0100 0000 - HRGF pulse detection12 2 Current Average MOTOR_I_AVE_SCALED:Average Motor Current Scaled.Scaled by parameter “I Scale Factor.”14 2 Voltage L1-L2 LINE_V_LL_AB_RMS:Phase A RMS Voltage L1-L2 (V)16 2 Voltage L2-L3 LINE_V_LL_BC_RMS:Phase B RMS Voltage L2-L3 (V)18 2 Voltage L3-L1 LINE_V_LL_CA_RMS:Phase C RMS Voltage L3-L1 (V)20 2 Voltage Average LINE_V_LN_AVE_RMS:Average RMS Voltage (V)22 2 Digital Inputs Bits 0-7 = Inputs for the first digital input cardBits 8-15 = Inputs for the second digital input card24 2 Digital Inputs Bits 0-7 = Inputs for the third digital input cardBits 8-15 = Inputs for the fourth digital input card26 10 Analog Inputs 5 Input words of data for analog inputs and status word(s)Input Instance 112 (0x70): Status, Current, Voltage, Trip with Analog and Digital Inputs, continuedLength = 36 BytesByteOffsetSize(bytes) Name Description