Appendix C—Optional Communication CardsPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 25332 4 Trip Reason STATUS_TRIPPED_BITS, continued0x0004 0000 - overload0x0008 0000 - stall0x0010 0000 - phase rotation mismatch0x0020 0000 - PTC0x0040 0000 - under voltage restart0x0080 0000 - peak demand0x0100 0000 - HRGF pulse detection36 4 Warning Reason STATUS_WARNING_BITSWarning/Alarm Indications0x0000 0001 - under voltage0x0000 0002 - over voltage0x0000 0004 - Reserved0x0000 0008 - ground current warning0x0000 0010 - current phase loss0x0000 0020 - current unbalance0x0000 0040 - instantaneous over current0x0000 0080 - jam0x0000 0100 - PF deviation0x0000 0200 - voltage phase loss0x0000 0400 - voltage unbalance0x0000 0800 - freq deviation fast0x0000 1000 - freq deviation slow0x0000 2000 - under current0x0000 4000 - high power0x0000 8000 - low power0x0001 0000 - Reserved0x0002 0000 - exceeds starts limit0x0004 0000 - overload0x0008 0000 - stall0x0010 0000 - phase rotation mismatch0x0020 0000 - PTC0x0040 0000 - under voltage restart0x0080 0000 - peak demand0x0100 0000 - HRGF pulse detection40 2 Thermal PilePercentageOVLD_THERMAL_MEM_PERCENT:Thermal Capacity0% Cold Motor100% Will Cause an Overload Trip (%)42 2 Digital Inputs Bits 0-7 = Inputs for the first digital input cardBits 8-15 = Inputs for the second digital input card44 2 Analog Inputs 1 Input word of data for an analog output card statusInput Instance 117 (0x75): Full Monitoring with Basic Analog and Digital Inputs, continuedLength = 46 BytesByteOffsetSize(bytes) Name Description