Appendix D—Modbus Register MapPower Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 339746 Control User Interface UserLED 3 PurposeUINT16 RW NVDefault: 1 EnumConfig CRCAdmin LockUSB LockBackup MemUser Defined LED 3 Function Selection - Default: Power Related Fault.Applies only to C445UC… Control Family of User Interfaces, continued.Table 128. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionValue Description24 Motor Control Status - Inhibited25 Motor Control Status - Warning26 Motor Control Status - Faulted27 Motor Control Status - Remote enabled28 Motor Control Status - Running 229 Motor Control Status - Running 130 Warning Status Bits - PTC31 Warning Status Bits - Phase rotation mismatch32 Warning Status Bits - Stall33 Warning Status Bits - Overload34 Warning Status Bits - Starts limit exceeded35 Warning Status Bits - Low power36 Warning Status Bits - High power37 Warning Status Bits - Under current38 Warning Status Bits - Frequency deviation slow39 Warning Status Bits - Frequency deviation fast40 Warning Status Bits - Voltage unbalance41 Warning Status Bits - Voltage phase loss42 Warning Status Bits - Power factor deviation43 Warning Status Bits - Jam44 Warning Status Bits - Instantaneous over current45 Warning Status Bits - Current unbalance46 Warning Status Bits - Current phase loss47 Warning Status Bits - Ground current48 Warning Status Bits - Reserved49 Warning Status Bits - Over voltage50 Warning Status Bits - Under voltage51 Tripped Status Bits - Under voltage52 Tripped Status Bits - Over voltage53 Tripped Status Bits - Reserved54 Base Control Module Field Output control word - Bit 055 Base Control Module Field Output control word - Bit 156 Base Control Module Field Output control word - Bit 257 Base Control Module Field Output control word - Bit 358 Shunt trip output bit - Shunt trip output bit59 Warning Reason - HRGF pulse detection60 Warning Reason - Peak demand61 Digital Input Status - Base Control Module Input I462 Digital Input Status - Base Control Module Input I363 Digital Input Status - Base Control Module Input I264 Digital Input Status - Base Control Module Input I165 Fail Safe - Ground current fault65535 Reserved