Appendix D—Modbus Register Map322 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com714 Local/Remote PowerUpBehaviorUINT8 RW NVDefault: 2EnumConfig CRCAdmin LockUSB LockBackup MemSelect the Local/Remote mode the Base Control Module will power up in.Selections: 0: Local control is active control on power up, 1: Remotecontrol is active control on power up, 2: Hold last control state onpower up.715 Q1 Function Select UINT16 RW NVDefault: 54EnumConfig CRCRun LockAdmin LockUSB LockBackup MemOutput Function Select for General Purpose Output 1. Available when thisoutput is not used by the Operation Mode. Default = none, If used by theApplication Mode = Reserved. A soft reset is required after modifying thisparameter.Table 128. C445 Modbus Register Map, continuedRegister Name Attribute DescriptionValue Description0 Local control is active control on power-up1 Remote control is active control on power-up2 Hold last control state on power-upValue Description0 None1 Fault Reason Type - Load fault (Power based)2 Fault Reason Type - Supply fault (Voltage based)3 Fault Reason Type - Motor fault (Current based)4 Tripped Status Bits - PTC5 Tripped Status Bits - Phase rotation mismatch6 Tripped Status Bits - Stall7 Tripped Status Bits - Overload8 Tripped Status Bits - Starts limit exceeded9 Tripped Status Bits - Low power10 Tripped Status Bits - High power11 Tripped Status Bits - Under current12 Tripped Status Bits - Frequency deviation slow13 Tripped Status Bits - Frequency deviation fast14 Tripped Status Bits - Voltage unbalance15 Tripped Status Bits - Voltage phase loss16 Tripped Status Bits - Power factor deviation17 Tripped Status Bits - Jam18 Tripped Status Bits - Instantaneous over current19 Tripped Status Bits - Current unbalance20 Tripped Status Bits - Current phase loss21 Tripped Status Bits - Ground fault22 Motor Control Status - Motor at speed23 Motor Control Status - Ready24 Motor Control Status - Inhibited25 Motor Control Status - Warning26 Motor Control Status - Faulted27 Motor Control Status - Remote enabled28 Motor Control Status - Running 229 Motor Control Status - Running 1