Appendix D—Modbus Register Map314 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com346 Run Time Lifetime UINT32 ROUnits: secondsBackup MemTotal motor run time in seconds348 Number Starts Lifetime UINT32 ROManufacturing LockBackup MemTotal Number of Motor Starts in lifetime, not resettable.350 Operating Seconds Lifetime UINT32 ROUnits: secondsBackup MemTotal number of Seconds the motor has been running. Not resettable.352 Run Time Resettable UINT32 RW NVDefault: 0Units: secondsAdmin LockUSB LockBackup MemTotal motor run time in seconds (Resettable). Resettable values can bezero-ed out by the user at any time.354 Number Starts Resettable UINT32 RW NVDefault: 0Admin LockUSB LockBackup MemTotal number of motor starts (Resettable).356 Operating SecondsResettableUINT32 RW NVDefault: 0Units: secondsBackup MemTotal number of Seconds the motor has been running since this valuewas last reset. This value is resettable.358 Contactor Operations LastHourUINT16 ROBackup MemNumber of Contactor Operations During the Last Hour359 Last Run Time UINT32 RODefault: 0Units: secondsDuration in Seconds of the Last Start-to-Stop Motor Run Time361 Last Starting Time UINT16 RODefault: 0Units: secondsThe amount of time the motor took to get up to speed on the last start.362 I Average % of FLA UINT16 ROUnits: %Monitored Average Motor Current as Percentage of FLA (NominalCurrent)363 Current Demand Value UINT32 ROUnits: WLatest estimate of the Demand measured over the demand windowduration.365 Demand (Resettable) UINT32 RW NVDefault: 0Range: 0 to 0Units: WAdmin LockUSB LockBackup MemPeak Demand, User Resettable. The peak demand is updated if thenew demand calculated over the demand window is greater than theprevious peak.367 Peak Demand Time Stamp UINT32 RODefault: 0Units: secondsAdmin LockUSB LockBackup MemPeak Demand Time Stamped (in Unix time)Table 128. C445 Modbus Register Map, continuedRegister Name Attribute Description